What a cultivation room actually draws, worked from a schedule

Last reviewed November 18, 2026 · 8 min read

The short answer

Airflow and under canopy lighting alone come to roughly 24 kW and 57.6 kW of connected load in the sample facility below, before top light, dehumidification or pumps. The fan total is 24 kW across sixty two fans, and the single largest line in it is not the big horizontal fans but the twenty two portable floor blowers, which add around 5.3 kW. Under canopy lighting is 120 fixtures at 120 W a room, so 14.4 kW per flower room and 57.6 kW across four. These are nameplate figures at the voltages the manufacturers publish. Demand load and service size are an electrical engineer's calculation, not a sum of nameplates.

Why the nameplate sum is not the answer

A schedule gives you connected load: what every piece of equipment would draw if all of it ran flat out at once. That is not what a service is sized on. An engineer applies demand factors, looks at what runs at the same time as what, and works from the actual duty cycle of each room. Lights in flower and lights in veg are rarely on the same schedule, and a floor blower on speed one is not a floor blower on speed three.

What the nameplate sum is good for is the conversation before the engineer. It tells you roughly what class of service you are in, it tells you which line items dominate, and it tells you whether the building you are looking at is plausible before anyone spends money on a load study.

Airflow: 62 fans, around 24 kW

Fan connected load, whole facility
FixtureQtyPublished drawApprox. eachApprox. total
Patterson 18in HV18A24208-230V, 3.0-2.9A660 W15,840 W
Patterson 14in HV14A7208-230V, 1.4A310 W2,170 W
Schaefer 8in VK8 in-rack9115V, 0.6A69 W621 W
B-Air VP-25 floor blower22115V, up to 2.1A240 W5,280 W
Total62~23,900 W

Two things fall out of that table. The first is that airflow is a real load, not a rounding error: twenty four kilowatts is a meaningful share of a cultivation service and it runs continuously, unlike lighting.

The second is the floor blowers. They are the cheapest fixture on the schedule and the only portable one, there are twenty two of them, and together they draw more than twice what the nine in-rack fans and seven smaller horizontal fans draw combined. At top speed each pulls around 2.1 amps on a 115 volt circuit. Four of them on one 20 amp circuit is already most of that circuit, and because they are portable they end up plugged into whatever outlet is nearest rather than the one they were drawn on.

Under canopy: 14.4 kW a room

The under canopy schedule in the sample set is 120 fixtures in one room, each published at 277 volts, 0.43 amps and 120 watts. That is 14,400 watts in a single flower room, and 57,600 watts across four identical rooms, for a system that is often treated as an accessory to the top light rather than a load in its own right.

Under canopy lighting, one room and four
FigureOne roomFour rooms
Fixtures120480
Watts per fixture120 W120 W
Connected load14,400 W57,600 W
Current at 277V~51.6 A~206 A
Runs832
Approx. current per run~6.5 A~6.5 A

The run count is what makes this manageable. Fixtures daisy chain up to twenty, which sets eight runs for a room of 120, and each run carries roughly six and a half amps. That is a sane circuit. The number to watch is the total, not the run: a flower room that adds under canopy adds the equivalent of twenty two more large horizontal fans to its connected load.

What is still missing from that number

  • Top light, which is normally the largest single load in the building and is specified on its own sheets.
  • Dehumidification, which is specified per room on the Q5 sheets and is the load that scales with how hard the rooms are run rather than with floor area.
  • Fertigation pumps, batch tank pumps and the fertigation skid.
  • Controls, sensors and anything on the building side: HVAC, lighting in corridors, processing and dry rooms.

Airflow and under canopy together are roughly 81 kW in this building. They are also the two systems most often left out of an early load conversation, because one is treated as an accessory and the other as a fan. Getting them on the sheet early is the difference between a service that was sized once and a service that gets upgraded during fit out.

Common questions

How much electricity does a commercial grow room use?

Airflow in the sample facility is around 24 kW of connected load across 62 fans, and under canopy lighting is 14.4 kW per flower room. Top light, dehumidification and pumps are on top of that. Connected load is not the same as a service size: an engineer applies demand factors and simultaneity before sizing anything.

How many amps do grow room fans draw?

On the sample schedule, an 18 inch horizontal fan is published at 3.0 to 2.9 amps at 208 to 230 volts, a 14 inch at 1.4 amps, an 8 inch in-rack fan at 0.6 amps at 115 volts, and a portable floor blower at up to 2.1 amps at 115 volts on its top speed.

How much power does under canopy lighting add?

The sample schedule runs 120 fixtures at 120 watts in one flower room, which is 14,400 watts, or roughly 51.6 amps at 277 volts spread across eight daisy chained runs at about 6.5 amps each.

Do I need an electrical engineer if I have the schedules?

Yes. The schedules give connected load, which is the starting point for a conversation. Demand factors, simultaneity, circuit design and the service size are a licensed engineer's work, and nothing on this page substitutes for it.

How we put this together

Equipment counts are read off the cultivation fan equipment schedule and the under canopy lighting equipment schedule in the EES sample set. Amperage, voltage and wattage are the manufacturers' published figures for each named fixture. Wattages are derived from the published voltage and current at the stated rating and rounded down.

Elevated specifies and supplies this equipment. Nothing here replaces a licensed electrical engineer, and the figures are connected load rather than a service size.